Leírás
-
Specifications Display Color transmissive LCD 320 x 240 pixels (70 mm diagonal) with 2 level backlight Power supply Battery type 1.5 V Alkaline AA MN 1500 or IEC LR6 x 6 Battery life typically > 10 hours (backlight on full)
> 12 hours (backlight reduced)Battery eliminator Input 110/230 V 50/60 Hz Output 15 VDC, 300 mA Ambient conditions (for indoor use only) Reference conditions All accuracies stated at 23°C ±1°C (73.4°F ±1.8°F) Operating temperature 0°C to 50°C (32°F to 122°F) Temperature coefficient of current ≤ ±0.15% of rdg per °C Temperature coefficient of voltage ≤ ±0.15% of rdg per °C Maximum relative humidity 80% for temperatures up to 31°C (87°F) decreasing linearly to 50% relative humidity at 40°C (104°F) Maximum operating altitude 2000 m Electrical safety Maximum safe working voltages Safety IEC 61010-1 600 V CAT IV double or reinforced insulation, pollution degree 2
Protection IP40; EN60529Current measurement 600 VAC rms or DC between uninsulated conductor and ground Voltage measurement 600 VAC rms or DC between either input terminal and ground, or 825 V between energized phase voltages (delta power config.) EMC Emission IEC/EN 61326-1:1997 A Immunity IEC/EN 61326-1:1997 Annex C Performance Criterion B Mechanical Dimensions (L x W x D) 300 x 98 x 52 mm (12 x 3.75 x 2 in) Weight including batteries 820 g (1.8 lb) Jaw opening 60 mm Jaw capacity 58 mm diameter Cleaning The unit can be cleaned with an Isopropanol impregnated cloth. Do not use abrasives or other solvents. Electrical data Accuracy 23°C ±1°C (73.4°F ±1.8°F). See Ambient conditions specifications for temperature coefficients. Current measurement (DC, DC rms, AC rms) Measuring range 0 to 2000 A DC or 1400 AC rms Autorange facility 40 A / 400 A / 2000 A Resolution 10 mA in 40 A range
100 mA in 400 A range
A in 2000 A rangeAccuracy: DC and DC rms I > 10 A ±1.5% rdg ±5 digits I < 10 A ±0.2 A Accuracy: AVG I > 10 A ±3% rdg ±5 digits I < 10 A ±0.5 A Accuracy: Pk I > 10 A ±5% rdg ±5 digits I < 10 A ±0.5 A Accuracy: AHr I > 10 A ±2% rdg ±5 digits I < 10 A ±0.5 AHr Accuracy: CF (Crest Factor) 1.1 ≤ CF < 3 ±3% rdg ±5 digits 3 ≤ CF < 5 ±5% rdg ±5 digits Resolution 0.01 Accuracy: RPL (Ripple) 2% ≤ RPL < 100% ±3% rdg ±5 digits 100% ≤ RPL < 600% ±5% rdg ±5 digits Resolution 0.1% I DC > 5 A, I AC > 2 A All measurements DC and 15 Hz to 1 kHz
Maximum overload 10,000 A or rms x frequency < 400,000
Amps rms is a true-rms measurement (AC + DC)Voltage measurement (DC, DC rms, AC rms) Measuring range 0 to 825 VDC or AC rms Autorange facility 4 V / 40 V / 400 V / 750 V Resolution 1 mV in 4 V range
10 mV in 40 V range
100 mV in 400 V range
1 V in 750 V rangeAccuracy: DC and DC rms V > 1 V ±1% rdg ±5 digits V < 1 V ±0.02 V Accuracy: AVG V > 1 V ±3% rdg ±5 digits V < 1 V ±0.03 V Accuracy: Pk V > 1 V ±5% rdg ±5 digits V < 1 V ±0.03 V Accuracy: CF (Crest Factor) 1.1 ≤ CF < 3 ±3% rdg ±5 digits 3 ≤ CF < 5 ±5% rdg ±5 digits Resolution 0.01 Accuracy: RPL (Ripple) 2% ≤ RPL < 100% ±3% rdg ±5 digits 100% ≤ RPL < 600% ±5% rdg ±5 digits Resolution 0.1% VDC > 0.5 V, VAC > 0.2 V All measurements DC and 15 Hz to 1 kHz
Maximum overload 1,000 V rms
Volts rms is a true-rms measurement (AC + DC)Harmonics THD (Total Harmonic Distortion) 1% ≤ THD < 100% ±3% rdg ±5 digits 100% ≤ THD < 600% ±5% rdg ±5 digits Resolution 0.1% DF (Distortion Factor) 1% ≤ DF < 100% ±3% rdg ±5 digits Resolution 0.1% H02 ≤ Vharm < H13 ±5% ±2 digits H13 ≤ Vharm ≤ H30 ±10% ±2 digits All measurements up to 30th harmonic (40th harmonic for 15 Hz to 22 Hz)
Frequency range of fundamental F0 15 Hz to 22 Hz and 45 Hz to 65 Hz
Vacrms > 1VWatts measurement (single and three-phase) (DC, DC rms, AC rms) Measuring range 0 to 1650 kW DC or 1200 kW AC Measuring range 4 kW, 40 kW, 400 kW, 1650 kW Resolution 1 W in 4 kW
10 W in 40 kW
100 W in 400 kW
1 kW in 1200 kWAccuracy 2.5% rdg ±5 digits
W1Ø < 2 kW ±0.08 kW
W3Ø < 4 kW ±0.25 kWVA measurement (single- and three-phase) (DC, DC rms, AC rms) Measuring range 0 to 1650 kVA DC or 1200 kVA AC Autorange facility 4 kVA, 40 kVA, 400 kVA, 1650 kVA Resolution 1 VA in 4 kVA
10 VA in 40 kVA
100 VA in 400 kVA
1 kVA in 1200 kVAAccuracy VA > 2 kVA 2.5% rdg ±5 digits VA < 2 kVA ±0.08 kVA VAR measurement (single- and three-phase) Measuring range 0 to 1250 kVAR Autorange facility 4 kVAR, 40 kVAR, 400 kVAR, 1200 kVAR Resolution 1 VAR in 4 kVAR
10 VAR in 40 kVAR
100 VAR in 400 kVAR
1 kVAR in 1200 kVARAccuracy VAR > 4 kVAR ±2.5% rdg ±5 digits VAR < 4 kVAR ±0.25 kVAR Power factor range 0.3 < PF < 0.99 Power factor (single- and three-phase) Measuring range 0.3 capacitive to 1.0 and 1.0 to 0.3 inductive (72.5° capacitive to 0° and 0° to 72.5° inductive) Resolution 0.001 Accuracy ±3° Frequency range 15 Hz to 1 kHz Displacement power factor (single- and three-phase) Measuring range 0.3 capacitive to 1.0 and 1.0 to 0.3 inductive (72.5° capacitive to 0° and 0° to 72.5° inductive) Resolution 0.001 Accuracy ±3° Frequency range 15 Hz to 22 Hz and 45 Hz to 65 Hz Kilowatt hour (kWHr) Measuring range 40,000 kWHr Autorange facility 4 kWHr, 40 kWHr, 400 kWHr, 4,000 kWHr, 40,000 kWHr Resolution 1 WHr in 4 kWHr Range
10 WHr in 40 kWHr Range
100 WHr in 400 kWHr Range
1 kWHr in 4,000 kWHr Range
10 kWHr in 40,000 kWHr RangeAccuracy kWHr > 2 kWHr ±3% ±5 digits kWHr < 2 kWHr ±0.08 kWHr All Watts /VA /VAR /PF measurements Frequency range DC and 15 Hz to 1 kHz Current range 10 A to 1400 A rms Voltage range 1 V to 825 V rms Maximum input 825 V rms / 1400 A rms Maximum overload 1000 V rms / 10,000 A All measurements DC and 15 Hz to 1 kHz. Maximum overload 10,000 A or rms x frequency < 400,000 Frequency measurement (from current or voltage sources) Measuring range 15 Hz to 1 kHz Resolution 0.1 Hz Accuracy 15 to 22 Hz ±0.5% rdg
40 Hz to 70 Hz ±0.5% rdg
15 Hz to 1000 Hz ±1% rdgCurrent range 10 A to 1400 A rms Voltage range 1 V to 825 V rms Scope function Current measurement Range 10 A / 20 A / 40 A / 100 A / 200 A / 400 A / 1000 A / 2000 A Resolution 1 A in 40 A
10 A in 400 A
50 A in 2000 AAccuracy ±3% rdg ±1 pixel Maximum overload 10,000 A Voltage measurement Range 4 V / 10 V / 20 V / 40 V / 100 V / 200 V / 400 V / 1000 V Resolution 100 mV in 4 V
1 V in 40 V
10 V in 400 V
31.25 V in 1000 VAccuracy ±2% rdg ±1 pixel Maximum overload 1000 V rms Frequency range DC and 15 Hz to 600 Hz Time base 2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms/div Refresh rate 0.5 seconds Maximum sampling rate 15.625 kHz Inrush current function Ranges 40 A, 400 A, and 2000 A Resolution 10 mA in 40 A range
100 mA in 400 A range
1 A in 2000 A rangeAccuracy I > 10 A ±5% rdg ±1 pixel I < 10 A ±0.5 A All measurements DC and 15 Hz to 1 kHz Maximum overload Maximum overload 10,000 A or rms x frequency < 400,000
Amps rms is a true-rms measurement (AC + DC)Capture time 1 s, 3 s, 10 s, 30 s, 100 s, and 300 s Maximum sampling rate 15.625 kHz Interface USB Interface to a PC Power Log software for download, analysis and reporting
345 Upgrade Utility for installing a new firmware versionLogging Memory Logging areas Three areas that can be used individually or combined into one large area Averaging periods 1 s, 2 s, 5 s, 10 s, 30 s, 1 min, 5 min, 10 min, 15 min, and custom Logging Times Volts and current mode Average time Logging time (1 area) 1 s 1 h 49 m 2 s 3 h 38 m 5 s 9 h 6 m 10 s 18 h 12 m 30 s 2 d 6 h 36 m 1 min 4 d 13 h 12 m 5 min 22 d 18 h 0 m 10 min 45 d 12 h 0 m 15 min 68 d 6 h 0 m Logging time (3 areas) 1 s 5 h 12 m 2 s 10 h 24 m 5 s 1 d 2 h 00 m 10 s 2 d 4 h 00 m 30 s 6 d 12 h 1 m 1 min 13 d 0 h 12 m 5 min 65 d 0 h 15 m 10 min 130 d 0 h 30 m 15 min 195 d 0 h 45 m V and A harmonics mode Average time Logging time (1 area) 1 s 0 h 34 m 2 s 1 h 8 m 5 s 2 h 52 m 10 s 5 h 44 m 30 s 17 h 13 m 1 m 1 d 10 h 26 m 5 m 7 d 4 h 10 m 10 m 14 d 8 h 20 m 15 m 21 d 12 h 30 m Logging time (3 areas) 1 s 1 h 38 m 2 s 3 h 16 m 5 s 8 h 11 m 10 s 16 h 23 m 30 s 2 d 1 h 11 m 1 m 4 d 2 h 23 m 5 m 20 d 11 h 25 m 10 m 81 d 0 h 50 m 15 m 121 d 13 h 15 m Single- and three-phase power mode Average time Logging time (1 area) 1 s 1 h 40 m 2 s 3 h 21 m 5 s 8 h 22 m 10 s 16 h 45 m 30 s 2 d 2 h 17 m 1 m 4 d 4 h 35 m 5 m 20 d 22 h 55 m 10 m 41 d 21 h 50 m 15 m 62 d 20 h 45 m Logging time (3 areas) 1 s 4 h 47 m 2 s 9 h 34 m 5 s 23 h 57 m 10 s 1 d 23 h 54 m 30 s 5 d 23 h 25 m 1 m 11 d 23 h 25 m 5 m 59 d 21 h 5 m 10 m 119 d 18 h 10 m 15 m 179 d 15 h 15 m